spottracker.blogg.se

Fluke network inspector key
Fluke network inspector key













For domestic and the testing of smaller installations, a multi-function installation tester will be sufficient. The inspector will require a range of test equipment to enable test results to be obtained. Personal Protective Equipment (PPE) may be required as specified in the RAMS or if required by the client for compliance with their own policy standards. For some clients the inspector may be required to provide a Risk Assessment and Method Statement (RAMS) for the inspection and testing work and for the RAMS to be site specific. The inspector will need to have an approved voltage tester and a lock off kit with a range of lock off devices and locks to be able to safely isolate the range of isolators, switches and circuit breakers likely to be encountered on the installation to be tested. For work on large and complex installations, access to other British Standards, IET Guidance Notes (such as Guidance Note 8: Earthing and Bonding), manufacturer’s data sheets and other information may be required. Additionally, access to a current edition of IET Guidance Note 3 would be advantageous. The inspector will need to have a sound working knowledge of the current edition of BS 7671 and it is essential they possess a current edition, or have access to it, for reference purposes. They will also further demonstrate that they have undergone training and education in inspection and testing with evidence of qualification(s) from a recognised examining body. To demonstrate competence, inspectors will need to have a high level of experience and knowledge of the type of installation to be inspected. BS 7671 defines a skilled person (electrically) as a “ person who possesses, as appropriate to the nature of work being undertaken, adequate education, training and practical skills, and who is able to perceive risks and avoid hazards which electricity can create”. Regulation 621.5 of BS 7671 requires: “ Periodic inspection and testing shall be undertaken by a skilled person or persons, competent in such work”.

fluke network inspector key

The Health and Safety Executive (HSE) also provides guidance on these regulations regarding technical knowledge and experience of working on particular systems. Regulation 16 of the Electricity at Work Regulations 1989 requires persons carrying out electrical work to be competent. Sadly, less than scrupulous contractors will knowingly send out non-competent persons, such as apprentices, friends and inexperienced electricians, to carry out inspection and testing. Questions often arise concerning the competence of persons carrying out inspection and testing.

fluke network inspector key

That is not the case now and these should now be recorded as non-compliances.

fluke network inspector key

For example, until 1966 it was acceptable to use a public water pipe as a means of earthing and Class I light fittings not to be earthed. Whilst this is true, it cannot be concluded that because something was acceptable in a previous edition of the Wiring Regulations it must be safe. It is often stated that the Wiring Regulations are not retrospective. When carrying out the inspection and test, the inspector should compare the installation for conformity with the current edition of BS 7671 and record any identified non-compliances. Testing is an ancillary activity to inspection, rather than the converse. It is essential for persons engaged in inspection and testing to understand that the inspection is more important than the testing. It is very important to note that Regulation 621.2 requires the installation to have a “ detailed examination” and that examination is to be “ supplemented by appropriate tests”.















Fluke network inspector key